What are the operating procedures for the frequency conversion series resonance test device? Wuhan UHV specializes in the production of series resonance, with a wide range of product selection and professional electrical testing. To find series resonance, choose Wuhan UHV.
1. When opening the box, the testing personnel shall inspect the equipment according to the packing list. If any discrepancies are found between the equipment and the packing list, please contact our company immediately
2. This test equipment should be used by high-voltage testing professionals. Before use, the user manual should be carefully read and repeatedly operated and trained.
3. The number of test personnel should not be less than 2. When using a high current generator, it is necessary to strictly follow your unit's safety operating procedures for high-voltage testing
4. In order to ensure the safety and correctness of the test, in addition to being familiar with the product manual, it is also necessary to strictly follow the relevant national standards and regulations for the test operation.
5. Each connecting wire must not be connected incorrectly, and the wiring must be connected according to the circuit diagram in the "Precautions" section, otherwise it may cause damage to the testing device
6. When this device is in use, it outputs high voltage or ultra-high voltage, and must be reliably grounded to ensure safe operation.
7. Before conducting the test on the test object, conduct a lift test on the equipment with a test voltage of 80% of the rated voltage of the equipment
8. Whether conducting a test on the test subject or a short rise test, the bottom section of the reactor must be separated from the ground with an insulated bracket
9. When conducting experiments, the distance between the variable frequency power supply and the reactor should be maximized as much as possible to avoid safety accidents
10. The variable frequency power supply part of this device is in the form of a touch screen. When tapping, it should be light and slow (with an interval of 0.5 seconds between entering the next menu). If the force is too heavy or the speed is too fast, it may not be able to enter the next menu or the machine may not start Press the reset button and return to the main menu. Restart after 5 seconds, or simply turn off the power and restart
11. When setting the parameters of the equipment, the "device voltage" column cannot be changed. "Device voltage" is set in conjunction with the voltage divider during factory testing If the "device voltage" is changed, the sampling signal of the voltage divider will change, and the measured voltage may not be the true test voltage, which may be too high or too low This has an impact on the withstand voltage test of the test sample So the experimenter should record the "device voltage" when starting up to avoid easy reference after the device voltage is accidentally activated
12. When conducting tests on test subjects with high capacitance or high loss, such as "generators, motors with large capacity, cables over 1.5km" The system Q value is low. Set the "output voltage" to between 30V and 50V. Generally, set the "output voltage" to between 10V and 20V When conducting cable tests below 10kV and within 500m in length, a lower excitation voltage should be selected, with the "output voltage" set to 10V. Otherwise, when searching for the resonance point, the test voltage will exceed the rated withstand voltage of the test object, resulting in a higher system Q value and easy breakdown of the test object