Power cables are often used as power input (or output) lines for power plants, substations, and industrial and mining enterprises, and are widely used in urban and rural power grids. Nowadays, cross-linked polyethylene insulation is mostly used. Due to the large capacity of the tested equipment, some places still use the direct current withstand voltage test method for the testing items of cross-linked polyethylene insulated power cables (hereinafter referred to as cross-linked cables) before operation. In recent years, many research institutions both domestically and internationally have shown that direct current testing can cause varying degrees of damage to cross-linked polyethylene cables.
Important issues in withstand voltage testing
A general principle of high-voltage testing technology is that the field strength of the test voltage applied to the specimen must simulate the operating conditions of high-voltage electrical appliances. The conclusion of passing or not passing the high-voltage test should represent whether the weak points in the high-voltage electrical equipment pose a threat to future operation. This means that the fault mechanism in the experiment should have the same physical process as the mechanism in electrical operation. According to this principle, the problems of conducting DC withstand voltage tests on cross-linked cables mainly manifest in the following aspects:
1) Under direct current voltage, the electric field strength is distributed according to the resistivity, and the material in the insulation layer of cross-linked polyethylene cable contains many components, and its resistivity distribution is uneven. At the same time, the resistivity is greatly affected by factors such as temperature. Therefore, under direct current voltage, the electric field distribution in the insulation layer of cross-linked polyethylene cable is uneven, which may result in strong electric fields in some parts of the insulation layer and weak electric fields in others, leading to local insulation breakdown and accidents during operation.
2) Cables generate a "memory" effect under direct current voltage, storing and accumulating unipolar residual charges. Once there is a "memory" caused by the DC withstand voltage test, it takes a long time to release this DC voltage. If the cable is put into operation before the residual DC charge is fully released, the DC voltage will be superimposed on the peak of the power frequency voltage, causing the voltage value on the cable to far exceed its rated voltage, which may lead to insulation breakdown of the cable.
3) The DC withstand voltage test of cross-linked polyethylene cables shows that due to the effect of space charge, the actual electric field strength in the insulation can reach more than ten times the working electric field strength of the cable insulation. Therefore, even if the cable passes the DC withstand voltage test without breakdown, it will still cause serious insulation damage.
4) The distribution of DC voltage electric field strength applied in the DC withstand voltage test is different from that of the AC voltage electric field strength during operation. The DC withstand voltage test cannot simulate the overvoltage that the cable is subjected to under operating conditions, and cannot effectively detect defects in the cable itself, cable joints, and construction technology. In recent years, due to the construction and renovation of urban and rural power grids, there has been an increasing number of cross-linked cables. The cable is only put into operation after the DC withstand voltage test, and there are also cases of cable or cable head breakdown occurring under operating voltage. Therefore, it is imperative to replace the original DC withstand voltage test with a non DC withstand voltage test to avoid damage to the cable caused by the DC test and ensure the safe and reliable operation of the cable.
Voltage withstand test method
There are several main methods for non DC withstand voltage testing, including:
1) The oscillation voltage test is conducted by charging with a DC power supply and discharging a series resistor and reactance through a discharge ball gap to obtain a damped oscillation voltage. This method is more effective than the DC withstand voltage test method, but still not as effective as the power frequency test.
2) Low frequency (0.1 Hz) withstand voltage test. Due to the large capacitance of the cross-linked cable being tested and the large capacity of the test transformer required for power frequency testing, the testing equipment is bulky and not suitable for on-site use. Using 0.1 Hz as the test power supply, theoretically the capacity of the test transformer can be reduced to 1/500, greatly reducing the weight of the test transformer. The test transformer can be moved to the site for testing. At present, this method is mainly applied to the testing of medium and low voltage cables. Due to the low voltage level, it cannot be used for testing high-voltage cables of 66 kV and above.
3) Resonant voltage withstand test. The adjustable inductance type resonance test system can meet the withstand voltage requirements, but due to its large weight and poor mobility, it is mainly used in laboratories. The frequency conversion resonance test method can meet the voltage resistance requirements of high-voltage cross-linked cables, and has the characteristics of light weight and good mobility, making it suitable for on-site testing.