What Conditions Do The Complete Set Of Frequency Conversion Series Resonance Test Equipment in The Power System Need To Meet

Oct 11, 2025 Leave a message

The complete set of frequency conversion series resonance test equipment applies the principle of series resonance. By adjusting the output frequency of the variable frequency controller, series resonance occurs between the reactor inductance L and the sample capacitance C in the circuit. The resonant voltage is the voltage applied to the sample.


If an arc suppression coil is connected to the neutral point of the system and its resonance condition is disrupted, the generation of resonance overvoltage can be effectively suppressed. The principle is also simple. The excitation inductance of the TV is relatively large (in the range of kiloohms to megaohms), while the inductance of the arc suppression coil is relatively small (in the range of hundreds of ohms). This makes it difficult to meet the resonance condition and resonance will not occur; On the other hand, if there is no arc suppression coil and intermittent arcing occurs during single-phase grounding, multiple charges and discharges on the capacitor can cause the TV to burn out and the fuse to melt; After adding the arc suppression coil, the capacitor discharges the small reactance, and the current in the TV is very small, so it will not burn out. Therefore, connecting the arc suppression coil at the neutral point has a good suppression effect on the ferromagnetic resonance overvoltage caused by the saturation of the voltage transformer iron core.

 

38


The series resonant automatic tuning grounding compensation device can achieve full compensation operation or very small detuning degree, mainly because a high-power damping resistor is connected in series in the primary circuit of the arc suppression coil, reducing the amplitude of the neutral point resonant overvoltage to 5%~10% of the phase voltage. Because if the capacitance current of the system is equal to the operating current of the arc suppression coil, that is, the neutral point voltage is limited below the allowable value during resonance, the full compensation mode can be achieved. This is the optimal working mode with minimal residual current. When grounded, the residual current is very small and will not cause arc overvoltage. Therefore, a high-power damping resistor can be connected in series in the primary circuit of the arc suppression coil to increase the damping rate. The detuning rate of the arc suppression coil is related to the voltage and damping rate of the power grid, After the formation of the power grid, its asymmetric voltage is basically a fixed value. To ensure effective suppression of arc overvoltage during single-phase grounding, the detuning rate of the arc suppression coil is required to be within ± 5%. Therefore, only by changing the damping rate can the displacement voltage be changed. Therefore, a resistor should be connected in series in the arc suppression coil circuit to ensure the damping rate and control the neutral point displacement voltage. In low-voltage power grids, due to the small asymmetric voltage at the neutral point, a specially designed neutral point dedicated transformer should be used to improve measurement accuracy and enhance detection sensitivity; The use of nonlinear resistors has a significant suppression effect on the overvoltage caused by wire breakage and transmission under under overcompensation.

Send Inquiry

whatsapp

Phone

E-mail

Inquiry