What is an 80kV VLF Tester?

 

It is a specialized instrument used for insulation diagnostics and withstand voltage testing of medium/high-voltage power cables (typically rated 10kV to 35kV or higher). Key features:

1.Output Type: Generates Very Low Frequency (VLF) AC high voltage, typically 0.1Hz sine wave or cosine-rectangular wave.

2.Rated Voltage: Maximum output voltage of 80kV peak (or equivalent).

3.Core Functions:

VLF Withstand Testing: Applies VLF voltage (e.g., 1.5–3×U₀) near/above operating voltage for 15–60 minutes to check insulation integrity. Destructive/qualification test.

VLF Tanδ (Dissipation Factor) Testing: Measures dielectric loss tangent (Tanδ), its increment (ΔTanδ), or dissipation factor (DF) to evaluate insulation aging, moisture, and degradation. Non-destructive diagnostic test.

Partial Discharge (PD) Measurement (optional): Locates insulation defects using dedicated sensors and software.

 

Key Components & Features

 

High-Voltage Generator: Converts low-voltage input to 0.1Hz/80kV output (resonant/PWM technology).

Control Unit: Touchscreen interface for parameter setup (voltage, frequency, duration), real-time monitoring (voltage, current, Tanδ), and data storage.

Measurement Unit: Precision sensors for voltage/current and Tanδ/capacitance calculations.

Accessories: HV cables, connectors, terminal adapters.

Safety Protections: Overvoltage/overcurrent protection, flashover detection, emergency stop, ground monitoring, interlocks.

Data Management: USB/Bluetooth/WiFi for report export and PC software analysis.

 

Selection Criteria

Cable Voltage Rating: 80kV suits cables rated 20kV, 25kV, or 35kV (U₀). Higher voltages (e.g., 66kV) require ≥130kV VLF testers.

Cable Length/Capacitance: Ensure testers' current capacity meets I=2πfCVI=2πfCV requirements.

Functions Needed: Withstand testing only? Tanδ diagnostics? PD measurement?

Waveform: Sine wave (closer to power frequency) vs. cosine-rectangular (higher efficiency). Verify project specifications.

Portability: Weight/size constraints for field use.

Power Supply: Input voltage (e.g., 220V single-phase).

Compliance: IEC, IEEE, or GB standards.

Brand/Support: Reliability and after-sales service.

 

HTY8204

 

Summary

The 80kV VLF tester is essential for acceptance, maintenance, and fault diagnosis of modern medium/high-voltage cables (especially XLPE). It delivers 0.1Hz AC voltage (up to 80kV) to detect insulation flaws effectively while enabling field portability. Selection requires matching cable parameters, test needs, and site conditions. Safety must always be the top priority.