Detailed Explanation Of The Reason Why Frequency Conversion Series Resonance Does Not Boost Voltage

Jul 22, 2025 Leave a message

In order to facilitate grid maintenance and improve electrical safety, high-voltage transmission and transformation equipment needs to undergo AC withstand voltage testing. However, the frequency conversion series resonance testing device is a measuring device used to achieve high voltage and large capacity, and can be used to test power cables, busbars, switches, etc. through reactors and excitation transformers, GIS, Perform power frequency withstand voltage testing on transformers and other equipment. The composition of compensation capacitors and main control devices is because the voltage, waveform, frequency, and electric field inside the insulation of the test object are consistent with the actual operation, and the test voltage is higher than the actual operation voltage. Therefore, the series resonance testing device is the most rigorous in determining the dielectric strength of electrical equipment. One of the most direct and effective methods.


There are two main reasons why the frequency conversion series resonance testing equipment does not boost voltage. For example, whether the boost point did not increase after finding the resonance point, or whether the boost did not increase during the search for the resonance point. By analyzing these two situations, determine whether there is a problem with the series resonance testing device itself or whether the insulation of the test item is damaged. For example, the first scenario is damage to the cable insulation layer (this possibility is very small, and if it is damaged, the resonance point cannot be found), and the second scenario is damage to the reactor you are using. This kind of hardware damage will definitely not increase.


Variable frequency series resonant device


Usually, it causes the series resonance of the frequency converter to not boost the voltage, and in most cases, there will be problems in finding the resonance point. The main reason for not finding the resonance point is that the capacitance and reactance of the specimen do not match, making it impossible to find the resonance point caused by resonance conditions exceeding the resonance frequency. In this situation, our solution is as follows:


1. Parallel compensation capacitors in the loop of series resonance testing equipment.


2. Adjust the series or parallel connection of the reactor to increase or decrease the inductance. Changing LC will generate resonance.


In the case of not boosting, the overvoltage protection and flashover protection parameters of the series resonant variable frequency power supply are set too small, which protects the testing equipment during the process of finding the resonance point and therefore cannot boost the voltage. In some cases, individual ground leaks can cause the boost to increase by half and cannot continue. At this point, the boost should be stopped and the wiring can be carefully checked before continuing the test.

 