The circuit breaker characteristic tester is often affected by various electromagnetic interference (EMI) during on-site testing, especially in operating substations or switch stations, resulting in waveform distortion, inaccurate measurement of time parameters, and even test failure. To effectively resist interference, systematic measures need to be taken, usually starting from the aspects of signal source, transmission path, and receiving end:
1. Reliable grounding:
Single point grounding: Connect the tester, sensor, and switch body to the same grounding point (main grounding grid).
Coarse short grounding wire: The instrument grounding wire should be thick, short, and firmly connected.
2. Strictly block:
Shielded wire must be used: All signal lines must use double-layer shielded cables.
Shielding layer single end grounding: The cable shielding layer is only grounded at the tester end, and the sensor end is suspended (key!).
3. Optimize wiring:
Try to be as short as possible: shorten the length of the signal line and avoid winding.
Stay away from interference sources: Keep away from high-voltage lines, CT/PT secondary lines, power cables, etc. When crossing, try to be vertical as much as possible.
4. Sensor selection and installation:
Preferred non-contact methods: such as grating rulers and laser sensors (with better anti-interference than sliding line resistors).
Stable installation away from strong magnetic fields: Keep away from areas with strong magnetic fields such as arc extinguishing chambers.
5. Utilize instrument functions:
Enable filtering: Adjust the hardware/software filtering strength based on the level of interference.
Differential input: Prioritize using differential input mode (if supported).
6. Ultimate means (strong interference):
Fiber optic isolation: using fiber optic transmission signals to completely cut off electrical interference paths.