Operation Method For AC Power Frequency Withstand Voltage Test

Jul 25, 2025 Leave a message

1, Operation method


(1) Connect the test transformer to the operation box (set) and the test object and accessories reliably. The casing and control console of the test transformer must be reliably grounded. The high voltage tail X end and measuring winding F end of the test transformer must be reliably grounded.

 

(2) The testing personnel shall clarify their responsibilities, clean up the on-site personnel (if possible, set up a shielding net), and assign a dedicated person to monitor and observe the status of the testing object.

 

(3) Check if the voltage regulator is at zero position and if the input power supply is normal. The test object should be clean and absolutely dry.

 

(4) Before the load test, an air lift test should generally be conducted. When the test product is not connected, increase the test voltage to calibrate various instruments and adjust the ball gap.

 

(5) Connect the power supply, slowly increase the voltage, closely monitor all instruments. When the voltage reaches the test voltage, start timing. After 1 minute, quickly reduce the voltage. Once the voltage drops to zero, cut off the power and replace the test product or end the test.

 

(6) During the process of boosting or withstanding voltage, if any of the following abnormal situations are found, the voltage should be immediately reduced and the power supply should be cut off. Stop testing and identify the cause:

 

① The pointer of the voltmeter swings very humanely:

 

② Discovery of burnt or smoking insulation;

 

③ The test sample has abnormal noise.

 

2, Complete set of power frequency withstand voltage accessories

 

(1) In the power frequency withstand voltage test, Rl should be selected based on the rated capacity of the transformer. For example, when the rated output on the high voltage side is 100-300mA, 0.5- Ω/N (test voltage) can be used. Water resistance is commonly used as a current limiting resistor. The length of the pipe can be considered as 150kV/m, and the thickness of the pipe should have sufficient heat capacity. (Preparation method of water-resistant solution: Mix distilled water swallowed with an appropriate amount of copper sulfate to prepare various resistance values).

 

(2) The set value of the ball gap is generally 110% to 120% of the tested tilt angle. The ball gap protection resistor can be selected as 1 Ω/V (test voltage). When the voltage exceeds the set value of the ball gap, the ball gap discharges. The product plays a protective role.

 

(3) In the power frequency withstand voltage test, the measured low voltage side voltage (instrument voltage) is not very accurate. The reason is that due to the leakage reactance of the test transformer, there will inevitably be a voltage drop or capacity increase, causing the voltage on the test sample to be lower than or higher than the voltage reflected on the low-voltage side instrument. In order to accurately measure the voltage applied to the test product, an RCF resistor capacitor oscillator is often connected to the high voltage side to measure the voltage.

 