The insulation resistance tester under UHV power can help many power workers conduct various power tests more conveniently.

(1) Check whether the insulation of the megohmmeter or insulation tester itself and the measuring circuit is good. The inspection method is to connect the grounding terminal of the megohmmeter or insulation tester to the ground wire, connect the measuring terminal to one end of the measuring line, suspend the other end of the measuring line, turn on the insulation output switch tester (or shake the megohmmeter to the rated speed), the insulation resistance reading is close to infinity, and the instantaneous short-circuit insulation resistance reading is zero.
(2) Short circuit all terminals of the high, medium, and low windings of the tested transformer with wires, and discharge the tested winding to ground and other windings before measurement
(3) Turn on the output switch of the insulation tester (or shake the megohmmeter to rated speed), quickly open the winding insulation resistance measurement circuit, and record the opening time.
(4) When the time reaches 15 seconds, immediately read the insulation R15 resistance value, and then read the R60 value after 60 seconds. To measure the polarization index, the testing time should be extended to 10 minutes, with one value read every minute and accurately recorded.
(5) When the end time is reached, remove the measuring wire from the transformer winding and connect it to the ground wire for discharge.
(6) Replace the wiring, complete the above procedure, and measure the insulation resistance of each winding.