Precautions For Selecting Protective Resistors For AC Withstand Voltage Testing

Sep 03, 2025 Leave a message

Wuhan UHV specializes in producing series resonance (also known as AC withstand voltage testing equipment). Next, we will share with you the precautions for selecting protective resistors for AC withstand voltage testing.

 

218


In the AC withstand voltage test, the high-voltage output terminal of the test transformer should be connected in series with a protective resistor to reduce the overvoltage at the outlet of the transformer's high-voltage winding when the test product flashes or breaks down. To limit short-circuit current.


The protective resistor is generally selected between 0.1~0.5 Ω/V and should have sufficient thermal capacity and length. The resistance should not be too large, otherwise it will cause significant voltage drop and power consumption during the normal operation of the circuit. The protective resistor can be a water resistor or a wire wound resistor. The strength of the insulation between turns should be taken into account for wire wound resistors to prevent inter turn flashover. Choose the length of the protective resistor so that it does not flash along the surface when the test object ruptures or flashover, and its length should be able to withstand the maximum test voltage with sufficient margin. The minimum length of the protective resistor can be selected according to the table below.


The protective gap connected in series with the protective resistor is usually set to 1 Ω/V, and the length of the resistor is also selected from the table.