Precautions for using the series resonance test device:
(1) Before using a series resonant device for voltage resistance testing, please measure the insulation resistance of the tested product according to the test procedure, and ensure that the tested product meets the relevant insulation requirements before entering the next stage of voltage testing.
(2) Before using a series resonant device for voltage withstand testing and starting the device, please recheck if the connection is correct, for example: the output voltage of the excitation transformer is connected to the lower end of the lower reactor through a grounded traction cable; The reactor on the high-voltage output line should be kept as far away as possible from the compensating capacitor and voltage divider. Do not approach the ground or surrounding objects to prevent high-voltage power lines from discharging to the ground and objects, because every small mistake you make can cause irreparable damage to equipment and personnel, and every time you correct a mistake, it is very valuable for the safety of on-site personnel and equipment;
(3) Due to the safety of personnel and equipment, there are high requirements for equipment docking. When connecting the substation grounding grid, pre-treatment should be carried out on the grounding piles, switchgear body, transformer shell dirt, rust, paint, etc. to ensure effective connection between the grounding wire and the grounding device. When there is no grounding device for on-site operations, a metal rod approximately 150cm long can be used, which can be buried in a relatively damp area on the ground. The underground depth should not be less than 120cm, and an appropriate amount of water should be injected if necessary to ensure reliable grounding of the equipment.
(4) The power supply of the series resonant equipment should use two 380 V fire protection lines. The 220 V power supply fire protection line for instrument operation should be separated from the 380 V fire protection line. The power supply line should avoid using welding machines and other equipment as much as possible to prevent interference. If a generator power supply is used, the neutral line should be grounded;
(5) Although we have conducted numerous simulation experiments or implemented various protective measures, the discharge of samples and the return of instrument overvoltage protection can cause damage to the instrument. However, there are many different global issues in the emission process, and there are many on-site instruments, as well as poor transportation and usage environments. Therefore, it is strongly recommended that you take measures to prevent earthquakes and dust in traffic, and read the precautions carefully.