As the name suggests, a series reactor refers to a reactor (inductor) connected in series in a circuit. In the industry of reactive power compensation and harmonic control, a series reactor mainly refers to a reactor connected in series with a capacitor. After the reactor and capacitor are connected in series, they form a resonant circuit, which plays a role in harmonic elimination or filtering. The role of the reactor in the resonant circuit is as follows:
1.1 Reduce the surge multiple and surge frequency of the capacitor bank. Reduce the surge multiple and surge frequency of the capacitor bank to protect the capacitors and facilitate the selection of supporting equipment. After installing a series reactor, the closing inrush current can be suppressed to below 1+square root of the reciprocal of the reactance rate. The national standard GB50227-2008 requires that the inrush current should be limited to less than 20 times the rated current of the capacitor (usually around 10 times). In order to avoid harmonic amplification (harmonic traction), it is required that the volt ampere characteristics of the series reactor be as linear as possible. When the network harmonics are small, use reactors that limit inrush current; A reactance rate of around 0.1% -1% can limit the inrush current to less than 10 times the rated current, reducing the active loss of the reactor. Moreover, the reactor has a small volume, occupies a small area, and is easy to install in a capacitor cabinet. The use of this type of reactor is both economical and energy-saving.
1.2 Form a fully resonant circuit with the capacitor bank to filter out characteristic subharmonics. After fully tuning the inductive reactance of the series filter reactor and the capacitive reactance of the capacitor, an AC filter with characteristic sub harmonics is formed to filter out a certain characteristic sub harmonic, thereby reducing the voltage distortion of that sub harmonic on the bus, reducing the characteristic sub harmonic current on the line, and improving the power quality of the network supplied to the bus.
1.3 Form a partial resonant circuit with the capacitor bank to suppress characteristic subharmonics. The prerequisite is to have a clear understanding of the harmonic situation in the power grid, identify whether there are large rectification equipment, electric arc furnaces, rolling mills and other loads that can generate harmonics in the surrounding power users, and whether there are high-performance high-voltage transformers and motors with poor performance. Try to measure the actual value of the harmonic in the power grid as much as possible, and then configure suitable reactors based on the actual harmonic components.
1.4 Increase short-circuit impedance, reduce short-circuit capacity, and decrease short-circuit current. The reactive power compensation branch is equipped with a series reactor in advance. When a capacitor fault occurs, such as capacitor plate breakdown or ground breakdown, the system provides short-circuit current through system impedance and series reactor impedance. As the impedance of the series reactor is much larger than the system impedance, it effectively reduces the short-circuit capacity of the capacitor during short-circuit faults, ensuring that the distribution circuit breaker can disconnect the short-circuit current and improving the safety and stability performance of the system
1.5 Reduce the discharge current from the capacitor bank to the faulty capacitor bank to protect the power capacitors. When the reactive power compensation capacitor bank in operation consists of multiple branches, if one of the capacitors fails, the other running capacitor banks will discharge through the faulty capacitor. Series reactors can effectively reduce this discharge surge and ensure the possibility of the protection device cutting off the faulty capacitor bank.
1.6 Reducing the switching inrush current of the capacitor bank and lowering the amplitude of the transient process of the inrush current is beneficial for the arc extinguishing of the contactor. During the process of switching capacitors with contactors, inrush current is generated. Series reactors can effectively suppress the transient process of operating current, which is beneficial for the disconnection of contactor contacts, avoiding arc reignition and causing overvoltage during operation. Reduce the amplitude of overvoltage, protect capacitors, and avoid overvoltage breakdown or insulation aging.
1.7 Reduce the amplitude of overvoltage caused by operating capacitor banks to avoid overvoltage protection in the power grid. During the process of switching capacitors with contactors, operational overvoltages are generated. Series reactors can effectively suppress the occurrence of contact breakdown in contactors, reduce the amplitude of operational overvoltages, protect capacitors, and avoid overvoltage breakdown or accelerated insulation aging. With the widespread application and development of power electronics technology, a large number of nonlinear loads have been added to the power supply system, such as low-voltage small capacity household appliances and high-voltage large capacity industrial AC/DC conversion devices, especially the use of static inverters. As they operate in a switching mode, they can cause distortion of the current and voltage waveforms in the power grid, leading to harmonic "pollution" of the power grid. Another important reason for the generation of harmonic "pollution" in the power grid is the impact and fluctuation loads connected to the grid, such as electric arc furnaces, large rolling mills, electric locomotives, etc. They not only generate a large number of high-order harmonics during operation, but also cause voltage fluctuations, flicker, and three-phase imbalance to become increasingly serious. This not only reduces the safety of the power supply equipment itself, but also seriously weakens and interferes with the economic operation of the power grid, forming a "public hazard" to the power grid. The comprehensive management of power quality should follow the principle of whoever pollutes should be responsible for the management, multi-level management, and hierarchical coordination. In the distribution and transformation system of the region, it is particularly important to select the main sources of power quality pollution and load centers that are sensitive to power quality to establish power quality control hub points, conduct online power quality monitoring at these points, and take corresponding measures to improve power quality.