Test Steps For Arc Suppression Coil Of Frequency Conversion Series Resonance Test Equipment

Oct 13, 2025 Leave a message

Test steps for arc suppression coil of frequency conversion series resonance test equipment


1. Based on the inductance of the arc suppression coil, estimate the capacitance uF of the phase shifting capacitor that needs to be matched, and then combine it in series or parallel to form the required capacitance.


2. Connect the wires as required, and after inspection, place the testing machine in place according to the division of labor.


3. After slowly adjusting the three-phase voltage regulator, when the terminal voltage of the arc suppression coil L is read from the electrostatic voltmeter V, the corresponding current is read from the ammeter A and recorded.


4. Adjust the voltage regulator to slowly reduce the voltage to zero, and then unplug the power switch.


5. Change the tap position of the arc suppression coil and adjust the capacitance of capacitor C to match the inductance value. Then repeat the test according to the above steps.


6. According to the number of voltmeters and ammeters. Draw the volt ampere characteristic curve of the arc suppression coil.

 

94


Attention should be paid to the arc suppression coil of the complete set of frequency conversion series resonance test equipment


1. When considering the inductance L value of a series resonant circuit, the inductance of the voltage regulator should be taken into account. The circuit inductance is the sum of the inductance value of the arc suppression coil and the inductance value of the voltage regulator. If the inductance value of the voltage regulator is not considered, the capacitor will not match. The working point is far away from the tuning point and the resonance amplitude is also low. When considering the inductance value of the voltage regulator, in general, the inductance of the arc suppression coil can be increased by 3.5% -4%


2. In a 35kV system, when single-phase grounding occurs, the highest voltage on the arc suppression coil is the phase voltage. That is to say, for the 220kV volt ampere characteristic test, the test voltage should also be increased to 22kV. For safety reasons, it is necessary to first conduct a power frequency withstand voltage test on the Zoomlion capacitors, with a test voltage of 24kV and a withstand voltage time of 1 minute.


3. During adjustment, in order to prevent resonance damage to the arc suppression coil, the protective ball gap Q (diameter 5cm) and water resistance (0.1 Ω/V) should be connected in parallel to protect the capacitor.


4. The regulator can only rise in one direction to avoid the influence of hysteresis. Each tap should be measured within the same range, and the range should not be changed in the middle to avoid affecting the accuracy of the test.


This method can be used for in-situ testing, with simple wiring, easy operation, safety and reliability, and can save energy consumption and testing costs.

Send Inquiry

whatsapp

Phone

E-mail