The Reason Why The Variable Frequency Series Resonant Withstand Voltage Test Device Cannot Boost The Voltage

Sep 12, 2025 Leave a message

The variable frequency series resonant voltage withstand test device is a voltage withstand test equipment for large capacity test samples in the power testing industry. It adopts the LC oscillation principle of inductance and capacitance, and can be assembled to complete the withstand voltage test of long-distance cables and high-voltage electrical equipment. In practical applications, the advantages of simple operation and easy portability are widely used in power engineering commissioning projects. Its control host variable frequency power supply can convert the current through AC → DC → AC conversion, and output it as a pure sine wave. The output frequency and voltage can be adjusted within a certain range, and it is the core control part of the series resonant boost test.

 

212


The frequency conversion series resonance withstand voltage test device undergoes strict quality inspection before leaving the factory. But why did the variable frequency power supply fail to increase the voltage when it arrived at the test site (i.e. the voltage did not reach the set value)? Below, we will analyze in detail what causes the fault phenomenon.


Reasons for the wiring of the variable frequency series resonance withstand voltage test device


1. Wiring error. According to the testing principle, the signal line of the variable frequency power supply should be connected to the acquisition signal column of the voltage divider. If there is a wiring error, it will cause the boost to fail. In this case, simply follow the operating instructions for series resonance and correctly wire each part to the test object to solve the boost problem.


2. The short circuit is broken. In the experiment, the excitation transformer and the reactor were connected through a short circuit to ensure the normal operation of the voltage boosting test. When the short circuit fails, it indicates that both the excitation transformer and the reactor cannot work properly, and the situation where the voltage cannot be raised is normal. Normally, manufacturers reserve some testing lines when shipping, in addition to those necessary for testing. Simply replace the faulty short-circuit wire to increase the voltage normally.


High voltage testing has a certain degree of danger. When conducting the test, it is necessary to strictly follow safety guidelines and operate each step correctly according to the equipment's user manual to avoid unnecessary failures and dangers. When the equipment malfunctions, it is necessary to consult professionals as soon as possible and eliminate professional guidance for troubleshooting. Do not blindly rely on confidence and disassemble and repair the equipment at will.