What Are The Protection Functions Of The Series Resonance Test Device?

Oct 23, 2025 Leave a message

Before using power cables, a series resonance test is required. At the same time, the series resonance test device has corresponding protection functions. Briefly introduced the protection function of the series resonance test device.

 

96


Flashover protection: When the sample undergoes discharge breakdown, the device quickly cuts off the output voltage while disconnecting the power supply. The load of the high-voltage circuit is released through the intermediate boosting transformer, which will not cause overvoltage or affect other equipment. "Flashover fault" is displayed on the screen of the control panel.


Overvoltage protection: The device can adjust the test voltage to prevent it from rising due to external reasons. When the test voltage exceeds the set value, the control panel automatically cuts off the circuit and prompts a voltage fault on the screen.


Overcurrent protection: In the event of a short circuit during the test, the control box quickly cuts off the power and prompts the screen to display "current fault".


Internal protection of equipment: When the internal equipment of the equipment is damaged, the thyristor in the DC circuit will quickly shut down. Cut off the DC power supply and cut off the AC power supply to prevent further expansion of the fault.


Quick disconnect protection: When the control circuit is short circuited, the main power switch is an air switch with quick disconnect function, which can cut off the fault and activate zero position protection: When starting the control box, the output terminal is always zero, there is no pulse signal, and no voltage output. When the test voltage is close to the test voltage (usually 90% of the test voltage), it is forbidden to adjust the inductance to prevent excessive voltage damage to the test product during the adjustment of the inductance.


Overload protection: When the output current exceeds the set current. The control box automatically shuts off the output. At this moment, there is a corresponding prompt.


Power outage protection: When the power is suddenly cut off. The system can use the remaining electrical energy in the circuit to promptly shut down the output signal. To ensure the safe shutdown of the system.


Disharmony protection: When the testing system loses resonance due to internal defects causing parameter changes, the console automatically shuts off the output.


Transportation seismic protection: The bottom of the control box is designed with an anti vibration disc spring to buffer the vibration caused by rough road surfaces.


The protection function of the series resonance test device can effectively protect the safety of the equipment during operation. However, in practical work, power workers still need to master the testing methods proficiently and strictly follow the instruments for testing.