SF6 Comprehensive Tester

SF6 Comprehensive Tester

The UHV-600 SF6 comprehensive tester integrates SF6 purity and SF6 decomposition product testing, consolidating functions that previously required two instruments into one instrument.

Product Introduction
Product Introduction

 

SF6 comprehensive tester is a highly integrated professional instrument designed for detecting the dew point, purity and decomposition products of SF6 gas. Its working principle is based on advanced technologies such as electrochemistry and infrared absorption, and it can accurately measure the moisture, purity and concentration of decomposition products in the gas.

 

 

 

Technique parameters

 

Purity Test range 0%~100%
Test accuracy ±0.5%
Test time <2min
Dew point Measuring range -80℃~+20℃
Measuring precision ±0.5℃(-60℃~+20℃)
Response time(+20℃) 63% needs 5sec 90% needs 45sec(-60℃~+20℃)
63% needs 10sec 90% needs 240sec(+20℃~-60℃)
H2S Measuring range 0~200ppm
Minimum value ≤0.1ppm
Measuring precision ±0.5%
Stability 0~200ppm
Repeatability ≤2%
SO2 Measuring range 0~200ppm
Minimum value ≤0.1ppm
Measuring precision ±0.5%
Stability 0~200ppm
Repeatability ≤2%
CO Measuring range 0~1000ppm
Minimum value ≤0.1ppm
Measuring precision ±0.5%
Stability 0~1000ppm
Repeatability ≤2%
Intake pressure 0~1.0 Mpa
Flow 0.01~1.00L/min
Ambient temperature -40℃~+60℃
Ambient Humidity 0~100% RH
Power AC 100~240V 50Hz or 60Hz
Built-in high capacity lithium-ion rechargeable battery
Battery performance Charging 8 hours can work for more than 8 hours.
Working temperature -30℃~+70℃
Size 280×140×300(mm)
Weight 6.8kg

 

Product Features
product-2000-1304

Excellent Gas Analysis Capability
The SF6 comprehensive tester is equipped with a highly sensitive gas sensor that can accurately identify and analyze the characteristics of SF6 gas. The detection purity can be accurate to four decimal places, with a minimum resolution of 0.01%.

Sturdy
The shell of the SF6 comprehensive tester is made of high-strength aluminum alloy, which can withstand 5000N external force impact without damage, effectively protecting the internal components.

Efficient Data Processing And Transmission
The SF6 comprehensive tester has a built-in high-performance processor that processes more than 1,000 sets of data per second. It is equipped with a wireless module with a transmission rate of 10Mbps, which can quickly transmit the analysis results to the designated device.

 

 

Common faults and troubleshooting

fault

Possible reasons

processing method

Dew point does not change

Gas not entering detector

Check the air circuit connection to see if the needle valve and flow valve are open

Open circuit of sensor connecting wire

Send to manufacturer for inspection

High dew point

Gas leakage

Use the leak detector to check whether the air circuit leaks

The instrument is placed for too long

Clean the air circuit with high-purity nitrogen for 30 minutes, activate the sensor

Reduced sensitivity

Send to manufacturer for calibration

Sensor failure

Send to manufacturer for maintenance

Low dew point

Sensitivity too high

Send to manufacturer for calibration

No change in SO2 and H2S

Gas not entering detector

Check air connection

Open circuit of sensor connecting wire

Check the connecting line

Sensor failure

Replace sensor

No decomposition products in gas

normal

he detection values of SO2 and H2S are low

There is air leakage in the internal air circuit of the instrument

Check gas path

Reduced sensitivity

Send to manufacturer for calibration

Sensor failure

Send to manufacturer for maintenance

The detection values of SO2 and H2S are too high

SO2 and H2S readings are unstable during detection

Sensitivity too high

Send to manufacturer for calibration

Filter failure

Send to manufacturer for maintenance

Sensor failure

Send to manufacturer for maintenance

 

Circuit fault

Send to manufacturer for maintenance

Charging indicator light does not light up

Circuit fault

Check circuit

Buzzer does not sound

Battery voltage too low

Charge

Buzzer failure

Replace buzzer

Circuit fault

Check the buzzer circuit

The buzzer keeps ringing

Circuit fault

Inspection instrument

LCD no display

Poor LCD connection

Check the connector

Battery voltage below 5.8v

Charge or replace the battery

Circuit fault

Send to manufacturer for maintenance

 

Product Application

Power Industry
SF6 comprehensive tester is mainly used in the power industry to detect the gas state in SF6 electrical equipment. It can accurately measure the purity, humidity, decomposition products and other parameters of SF6 gas to ensure the safe and stable operation of the equipment.

Industrial Gas Detection Field
In the field of industrial gas detection, SF6 comprehensive tester can conduct comprehensive detection of SF6 gas to determine whether the gas is pure, whether it contains impurities or other harmful gases, and ensure the quality and safety of SF6 gas in industrial production.

product-2000-1304
product-2000-1304
product-2000-1304
product-2000-1304
product-2000-1304
product-1500-978
product-1500-978
product-2000-1304
product-2000-1304
product-2000-1304
product-2000-1304

We are a professional SF6 Comprehensive Tester manufacturers/SF6 Tester manufacturers in China.We can provide the best professional SF6 Comprehensive Tester for sales and competitive price. If you are looking for SF6 Tester supplier, we are a good choice.


Contact us to get SF6 Tester price.

Hot Tags: sf6 comprehensive tester, China sf6 comprehensive tester manufacturers, suppliers, factory, dissipation factor tester, PT analyzer, , primary current injection test set, , Interfacial tensiometer

Send Inquiry

You Might Also Like

    whatsapp

    Phone

    E-mail

    Inquiry

    Bag