Method for Eliminating Sparks in Contact Points of SF6 Density Relay

Jun 20, 2023 Leave a message

Due to the low contact current of SF6 density relays, there will be no arcing between the contacts. Sparks at the contacts are caused by inductance in the contact circuit. When the contact is disconnected, overvoltage will occur on the inductance. Overvoltage and power voltage discharge through the just separated gap on the contact gap. Due to energy limitations, spark discharge is the only phenomenon. The displacement and conversion of energy in the capacitance and inductance between the contacts cause spark discharge to flicker, becoming a high-frequency signal.
Furthermore, spark discharge can also cause contact damage and reduce service life, so it is necessary to eliminate it.
There are two effective spark suppression circuits:
1. Its working principle is to make the energy in the inductor pass through RC (Resistance Capacity) instead of the contact.
2. The second working principle is that energy is dissipated on the load through the diode when the contact is disconnected.
You can choose a method in practice. Please pay attention to selecting the RC with appropriate parameters, mainly determined through experiments. RC can generally be selected based on the load current 1a/1 micro method. When using diodes, the positive and negative poles should be connected correctly.
If a contact load cannot meet the application requirements, multiple pairs of contacts can be processed in parallel. Adjust the contacts before use to make the synchronization meet the requirements. The best approach is to choose a central SF6 relay or contactor to increase the load on the contacts.

 