1. Working Principle: Series Resonance
In a series resonant circuit, the inductive reactance (XL) of a high-voltage reactor and the capacitive reactance (XC) of the cable under test cancel each other:

Solving for frequency:

At resonance:
The test voltage is maximized across the cable with minimal power input.
The system acts like a voltage magnifier.
Reactive power is circulated, only small active power is drawn from the supply.
2. Key System Components (Detailed)
| Component | Function | Key Notes |
|---|---|---|
| Variable Frequency Power Supply (VFPS) | Supplies power at tuned frequency (20–300 Hz) | Often solid-state inverter; precise control of output frequency |
| Excitation Transformer | Steps up low voltage from VFPS | Insulation must withstand HV side output |
| HV Reactor (Inductor) | Forms LC resonance with test object | Must be variable or modular to handle different capacitances |
| Test Object (Cable) | Provides the test capacitance | Long cables = high capacitance, typically 0.1–5 µF |
| HV Divider | Measures output voltage accurately | Capacitive or resistive divider; calibrated |
| Control & Protection System | Monitors operation, logs data, trips on fault | Includes overvoltage, overcurrent, PD threshold alarms |
3. System Configurations
A. Modular Containerized System
Mounted in truck or container
Used for field testing of long-distance HV power lines (e.g. 220kV, 400kV)
Can test 1–10 km cables
B. Mobile Skid-Based System
Compact for medium-voltage applications
Easily transported via trailer or pickup
Lower output: 50–150 kV
4. Typical Testing Process
| Step | Description |
|---|---|
| 1. Preparation | Measure cable length, capacitance, check termination, ground shield |
| 2. Resonance Tuning | Adjust frequency until maximum voltage appears across the cable |
| 3. Voltage Ramp-Up | Increase voltage to test level (usually 1.7–2.0× U₀ of cable) |
| 4. Soak Period | Maintain full test voltage for 15–60 minutes |
| 5. Monitoring | Monitor voltage, current, PD (optional), temperature |
| 6. Discharge | Properly discharge the cable before ending test |
5. System Sizing Guidelines
To select the correct system, calculate the load capacitance and test requirements:
A. Cable Capacitance Estimation:
![]()
B. Required Test Power:
![]()
V: Test voltage (rms)
f: Frequency (Hz)
C: Total capacitance (µF)
Q: Reactive power (kVA)
C. Example:
Cable: 5 km, XLPE, 220kV class
Capacitance: 0.25 µF/km × 5 = 1.25 µF
Test voltage: 1.7 × √2 × 127 kV ≈ 305 kV (peak)
Frequency: 50 Hz
Q=2π×50×(305×103)2×1.25×10−6≈36MVARQ = 2\pi × 50 × (305 × 10^3)^2 × 1.25 × 10^{-6} ≈ 36 MVARQ=2π×50×(305×103)2×1.25×10−6≈36MVAR
The resonant system must support this reactive power at the desired voltage.
6. Advanced Options
Integrated Partial Discharge (PD) Analysis
Detect early insulation defects
Tan δ (Dissipation Factor) Measurement
Insulation aging analysis
Remote Control & SCADA Integration
For automated testing, record keeping, and cloud reporting
HV Filter (Harmonic Suppression)
Prevent EMI disturbances during resonant tuning
7. Standards and Pass Criteria
| Standard | Voltage Level | Test Duration | Pass Criteria |
|---|---|---|---|
| IEC 60840 | 30–150kV | 1h at 2× U₀ | No breakdown |
| IEC 62067 | 150–500kV | 1h at 2× U₀ | No breakdown |
| IEEE 400.4 | All | Typically 30–60 min | Optional PD < 5 pC |
8. Applications
Factory Acceptance Testing (FAT) & Site Acceptance Testing (SAT)
Commissioning of long underground power transmission lines
HVDC cable sheath testing (at AC)
Submarine cable verification
Cross-bonded cable circuit section testing
9. Comparison: AC Resonant vs Other Methods
| Feature | AC Resonant | AC Test Transformer | VLF Test | DC Test |
|---|---|---|---|---|
| Suitable for long cables | ✅ | ❌ (too bulky) | ✅ | ❌ (damaging for XLPE) |
| Power required | Low (resonant) | High | Very low | Low |
| PD Measurement | ✅ | ✅ | Limited | ❌ |
| Weight/Portability | Medium | High | Light | Light |
| Use on XLPE cable | ✅ | ✅ | ✅ | ❌ |